Testing and Replacing an AC Dual Run Capacitor

Fix an outdoor fan or compressor that hums but refuses to spin up. Follow these step-by-step instructions to troubleshoot and complete the fix safely.

Safety Warning

SHOCK HAZARD: Capacitors store lethal electrical charge even when disconnected. Discharge across terminals with an insulated screwdriver before touching.

Tools Needed

  • Multimeter with capacitance (µF) setting
  • Nut driver
  • Insulated screwdriver

Materials Needed

  • Exact replacement dual run capacitor (e.g. 45/5 µF 440V)

Step-by-Step Instructions

1

Disconnect Outdoor Power

Pull the outdoor disconnect block and flip the breaker in the main electrical panel.

2

Remove Electrical Access Panel

Unscrew the corner metal panel on the condenser unit to expose the cylindrical silver capacitor.

3

Discharge Terminals Safely

Hold a screwdriver by its rubber insulated handle. Bridge the metal blade across HERM to COMMON, and FAN to COMMON terminals to spark-discharge.

4

Photograph Wire Connections

Take a close-up photo showing which colored wires connect to HERM (compressor), FAN (fan motor), and C (common).

5

Measure Capacitance with Multimeter

Disconnect wires. Touch meter probes between C and HERM, then C and FAN. Readings should be within ±5% of labeled rating.

6

Install Exact Replacement

Transfer wires to matching terminals on the new capacitor and screw retaining strap tight.

When to Call a Professional

  • If replacing the capacitor does not start the motor, the compressor motor windings are seized or burned out.

DIY Cost

$15 - $30

Professional Cost

$150 – $450+